Cooling capacity is one of the most important criteria when selecting a chiller; however, do two chillers with the same cooling capacity necessarily have similar power consumption and performance?

The answer is no. Meeting the required cooling capacity is only one part of the design challenge. Compressor selection, evaporator and condenser design, refrigeration cycle operating conditions, and capacity control methods can all affect a chiller’s energy efficiency and operating costs.

For example, two chillers may each have a cooling capacity of 500 kW, yet one may require less electricity to deliver this amount of cooling or provide better performance under partial-load conditions.

To compare these two designs accurately, identical operating conditions must be considered. In addition to cooling capacity, power consumption, efficiency, and equipment performance under actual operating conditions must also be evaluated.

1. The Role of Operating Conditions in Chiller Performance

The performance of a chiller depends largely on the refrigerant’s evaporation and condensation conditions. The refrigerant absorbs heat in the evaporator and rejects heat to the surroundings in the condenser. The compressor increases the refrigerant pressure, enabling the cycle to continue.

Two important parameters in this process are the refrigerant evaporation temperature and condensation temperature.

In general, under comparable conditions, increasing the evaporation temperature or decreasing the condensation temperature can improve the compressor’s operating conditions and reduce its required power. Conversely, a lower evaporation temperature or a higher condensation temperature generally makes the compressor’s task more demanding.

However, the actual magnitude of these effects depends on the refrigerant type, compressor type, cooling load, and manufacturer’s permitted operating range.

Therefore, compressor selection should not be based solely on its nominal capacity. It is necessary to determine the capacity the compressor can deliver at the temperatures and pressures required by the project and the power it consumes under those conditions.

For evaluating the performance of vapor-compression chillers, AHRI Standard 551/591 (SI) provides a framework for determining and rating equipment capacity and efficiency under specified conditions. Using identical test conditions enables a more reliable comparison between two chillers. (1)

Chiller Design and the Balance in Chiller Design

2. Heat Exchangers: The Impact of Design on Energy Consumption

The evaporator and condenser are the two main heat exchangers in a chiller. Their design affects the refrigerant’s evaporation and condensation conditions and can therefore change the compressor’s energy consumption.

One of the indicators used to evaluate the thermal performance of these heat exchangers is the temperature difference between the fluid and the refrigerant, known as the Approach Temperature.

Evaporator Approach Temperature

In a conventional chilled-water evaporator, this temperature difference is generally determined using the following relationship:

In this relationship, the two parameters are the chilled-water outlet temperature from the evaporator and the refrigerant saturation temperature at the reference evaporation pressure.

Simply put, this indicator shows how much higher the outlet water temperature is than the refrigerant evaporation temperature. Under similar design conditions, a lower Approach can indicate more effective heat transfer and make operation at a higher evaporation temperature possible.

However, it must be clear which pressure point is used to calculate the saturation temperature, because refrigerant pressure drop across the evaporator can cause the saturation temperature to vary along the flow path.

Condenser Approach Temperature

The definition of this indicator depends on the type of condenser.

  • In water-cooled chillers: The difference between the refrigerant condensing temperature and the condenser water outlet temperature can be used to evaluate thermal performance, provided that this basis is adopted in the selected evaluation method.
  • In air-cooled chillers: The difference between the refrigerant condensing temperature and the air temperature entering the condenser is one of the indicators used to evaluate heat-transfer conditions.

Under identical conditions, a smaller temperature difference can make operation at a lower condensing temperature possible. This generally helps reduce the compression ratio and compressor power consumption.

However, reducing the Approach does not always mean a more economical design. Achieving it may require a larger heat-transfer surface, a larger heat exchanger, a higher fluid flow rate, or more powerful auxiliary equipment. These changes can increase initial costs and the electricity consumption of fans or pumps.

Therefore, an appropriate design must strike a balance among heat transfer, pressure drop, dimensions, initial cost, and energy consumption.

In addition to chiller performance-rating standards, ANSI/ASHRAE/IES Standard 90.1 is also used to establish minimum energy-efficiency requirements for buildings and related mechanical systems, including certain cooling equipment. Its specific requirements depend on the edition of the standard, the equipment type, and the conditions of application. (2)

3. Compressor Selection and Coordination of System Components

The compressor, evaporator, and condenser are not independent components; the performance of each affects the operating conditions of the others.

For example, if the evaporator design allows the refrigerant to evaporate at a higher temperature, the compressor may be able to meet the same cooling load with less power. Similarly, if the condenser can reject heat under more favorable conditions, a reduction in condensing temperature can help improve compressor performance.

However, these benefits can only be evaluated when the performance of the entire system is considered. Changes in heat-exchanger surface area, fluid flow rate, or pressure drop can also affect the performance of other components.

The compressor type is also important. Reciprocating, screw, and scroll compressors have different performance characteristics, and their behavior at different loads is not identical. Furthermore, capacity control methods, such as variable-speed operation or staged control, can affect energy consumption under partial-load conditions.

Therefore, selecting a high-efficiency compressor or a heat exchanger with a larger heat-transfer surface does not, by itself, guarantee better chiller performance. The final outcome depends on how well the components work together under actual operating conditions.

4. Power Consumption and Part-Load Performance

To compare the electricity consumption of two chillers, it is first necessary to determine whether the power consumption under consideration refers to compressor power or the total power consumption of the entire unit.

Compressor power accounts for only part of a chiller’s electricity consumption. Depending on the equipment type, condenser fans, internal pumps, and other auxiliary equipment may also contribute to power consumption. When evaluating the total system energy consumption, external equipment such as water-circuit pumps and the cooling tower must also be included within the calculation boundary.

Furthermore, a chiller’s performance at rated load does not necessarily indicate its performance throughout the year. Many chillers operate for a significant portion of their operating hours at loads below their rated capacity.

Under these conditions, the compressor type, capacity control method, ambient temperature, condenser entering-water temperature, and equipment control strategy can create significant differences in energy consumption.

AHRI Standard 551/591 (SI) defines indicators for evaluating performance at full load and part load. One of these indicators is the Integrated Part-Load Value (IPLV), which evaluates a chiller’s energy performance at several standardized operating points using specified weighting factors.

This indicator is useful for comparing chillers under defined conditions, but it does not necessarily represent the unit’s annual energy consumption in an actual project. This is because weather conditions, building load profiles, operating hours, and system control methods may differ. Other indicators and evaluation methods may also apply under newer standards or specific application conditions. (1)

Therefore, for a more accurate selection, part-load performance and the energy consumption of auxiliary equipment should be evaluated in addition to cooling capacity and full-load efficiency.

5. Conclusion: The Same Capacity Does Not Necessarily Mean the Same Performance

Two chillers can have the same cooling capacity but different electricity consumption and operating costs because of differences in compressor selection, heat-exchanger design, refrigerant evaporation and condensation conditions, and capacity control methods.

AHRI Standard 551/591 (SI) provides a framework for rating chiller performance under specified conditions, while ASHRAE 90.1 establishes minimum energy-efficiency requirements within its scope of application. Nevertheless, the appropriate design must be selected based on the project’s specifications and actual operating conditions.

No single parameter, whether cooling capacity, heat-exchanger temperature difference, or compressor efficiency, is sufficient on its own to determine the superiority of a design. A reliable evaluation must consider power consumption, operating conditions, part-load performance, and, where necessary, the energy consumption of auxiliary equipment together.

At Form Dama, the design and selection of cooling equipment are based on an assessment of project operating conditions, engineering calculations, and the coordinated evaluation of system components. Required capacity, temperature conditions, compressor and heat-exchanger performance, energy consumption, and relevant technical requirements and standards are among the factors considered during the equipment design and selection process.

Under this approach, the final selection is not based solely on the initial purchase price. The suitability of the equipment for the project’s actual needs, expected performance, and operating costs are also important considerations in the decision-making process. The objective is to provide an engineered solution that meets the required capacity and operating conditions while establishing an appropriate balance among initial cost, energy consumption, and operating requirements.

Technical References

(1) AHRI Standard 551/591 (SI)

Performance Rating of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle

This standard specifies methods for rating the performance of chiller and heat-pump packages covered by its scope.

(2) ANSI/ASHRAE/IES Standard 90.1

Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings

This standard establishes minimum energy-efficiency requirements for buildings and systems covered by its scope of application.